Cooling calculations & sources

Plant

Mechanical cooling · setpoint met

Liquid duty
2,070 / 2,070 kW · delivered / requested
Facility water
73°F → 92°F
Primary flow
2880 L/min
Secondary flow
2150 L/min
External Δp
161 kPa · assumed system curve
Compressor
207 kW · estimated COP 10.0
Pumps + fans
37 kW · estimate; heat excluded
Residual air load
306 kW · separate air system
Liquid heat rejection
2,277 kW
Tower water
85°F → 93°F
Evaporation
11.9 GPM · 80% latent assumption
Blowdown
3.9 GPM · 4 cycles
Total makeup
15.8 GPM · includes drift

GB200 NVL72

Blackwell · 2025

18 compute + 9 NVLink trays; 72 GPUs, 36 CPUs. Design assumptions: 82°F supply, 132 kW rack, 115 kW liquid.

Supply water
82°F
Return water
107°F · ΔT 25°F
Loop flow
568 GPM · 119 L/min per rack
Per GPU
1,200 W · 4,095 BTU/h
Per rack
132 kW · 115 to water · 17 air
18 racks
2.4 MW · 8.1 MBTU/h · 676 tons
Junction estimate
127°F · uncalibrated

Die basis: assumed junction-to-mean-water resistance 0.027 °F/W; no verified throttle limit.

Q = kW × 3,412 BTU/h · ΔT = Q ÷ (500 × GPM) · tons = Q ÷ 12,000
Model basis & sources

Design-point explainer, not an OEM equipment selection. Treated water: 995 kg/m³, 4.18 kJ/kg·K. No glycol/freeze model. Sea level, 5–46°C outdoor range. Wet bulb uses an approximate ventilated-psychrometer relation.

Rack powers, GPU TDP, thermal resistance, pipe sizes, pump system curve, 3 MW plant rating and COP are assumptions. Temperatures at a capacity limit describe the deliverable load only. Auxiliaries are reported separately; their heat is outside the liquid balance. Residual rack air cooling is outside this plant.

Trane centrifugal chiller / water-box arrangement
Water-box isolation and service principles. Internal geometry here is representative.

Baltimore Aircoil / counterflow towers
Opposed air/water flow, fill, and overhead spray distribution.

NVIDIA Blackwell / two-die GPU
Two linked dies per Blackwell GPU package. Floorplan and package scale are illustrative.

NVIDIA GB200 hardware / tray inventory
Published inventory; cabinet dimensions are representative.

NVIDIA Vera Rubin / 45°C inlet
Published inlet and dry-cooling capability; remaining Rubin values are assumptions.

Vertiv XDU1350 planning guide
Cabinet dimensions and 20 L/s dual-pump reference. 1,350 kW at 5 K is a conservative scenario, not an OEM rating.

DOE cooling tower water balance
Makeup = evaporation + blowdown + drift.